Request documents
ESS · Containerized enclosures · Battery racks

Energy Storage Systems

KEMP develops Innozinc surface-treatment specifications for ESS enclosure frames, door hardware, brackets and fasteners. Production experience with angles and channels supports component-specific process design for corrosion protection and dimensional control. Sample assessment covers outdoor exposure, bonding continuity and electronics-related component requirements.

1,000hr
Reference scratch test
No red rust observed
Electrodeposited zinc
Metallic base layer
Joint resistance requires testing
25
Ambient-temperature process
Reduced heat-distortion risk
26analytes
Chemical screening
Confirm report scope and limits
Special-container structures Production references Door gear Comparable container hardware Cut and damaged edges Review sacrificial protection Thread fit Verify coating allowance Hexavalent chromium Cr(VI)-free specification available
Innozinc automated plating line at KEMP's Ulsan plant
Ulsan plant: Innozinc automated plating line. Electrodeposition at approximately 25°C reduces heat-related distortion risk; confirm the complete process for the selected part.
Three Constraints

Three ESS design requirements

Corrosion, electrical safety and contamination control must be considered together with loads, maintenance and approval requirements.

CONSTRAINT 01

Earthing and bonding continuity

Enclosure, doors and racks may require equipotential bonding. Coatings, contact geometry and assembly affect connection resistance. Verify the complete bonded joint; do not assume conductivity from the coating family alone.

Validate the assembled electrical connection
CONSTRAINT 02

Long-term outdoor durability

Corrosion may remain unnoticed between inspections. Define exposure, maintenance access, design life and dimensional tolerances before selecting a coating.

Review the service-life evidence below
CONSTRAINT 03

Electronics inside the enclosure

Conductive particles near batteries, PCS and BMS can cause electrical faults. Internal components need contamination and whisker-risk review as well as corrosion assessment.

Review internal-component requirements below
Selection approach

Specify by component and exposure

Review external, foundation and internal components separately. Internal parts need electrical and contamination requirements defined before coating approval.

See the component guidance below
Grounding & Bonding

Bonding performance
depends on the complete joint

For hinges, door gear and earthing brackets, confirm contact resistance, assembly torque, contact preparation and ageing behaviour. Salt spray hours alone cannot establish electrical suitability.

Table 1

Coating considerations for ESS

Indicative process comparison—not an approval matrix
ItemPowder coatingZinc flake coating (ZFC)Hot-dip galvanizing (HDG)Electro-zinc + conversion coatingInnozinc
Earthing / electrical continuityProvide and test a bonding pathSystem-dependentTest coated joint resistanceVerify assembled jointVerify assembled jointVerify by testingMetallic zinc under an inorganic layer
Thermal processingCuring requiredTypically thermally cured; confirm TDSHot-dip immersion; bath temperature and post-treatment specified for the componentConfirm the complete processAmbient electrodeposition, approximately 25°C
Cut edges / damageRepair or edge protection requiredSystem- and damage-dependentZinc sacrificial protection; assess damageZinc sacrificial protection; assess damageZinc sacrificial protection; assess damage
Thread allowance / overtappingAllow for coating thickness and verify thread fitConfirm thread fitSpecify coating allowance and compatible nutsConfirm thread fitVerify coated thread gauges
Heat-related distortion riskDepends on curing and geometryDepends on curing and geometryAssess hot-dip thermal effectsReduced thermal exposure; assess partReduced thermal exposure; assess part
Hexavalent chromium (Cr(VI))Confirm material compliance requirementsSpecification-dependentConfirm post-treatment specificationConfirm conversion-coating chemistryCr(VI)-free specification available
Hydrogen embrittlement considerationsAssess material and pretreatmentNon-electrolytic deposition; assess pretreatmentAssess material and pretreatmentControl pretreatment and electrodepositionQualification requiredElectroplating process; see application limits

Electrical continuity requires measured evidence. A metallic zinc base layer does not establish an acceptable assembled-joint resistance. No qualifying contact-resistance result is provided here. Agree testing on your parts at the specified assembly torque, including ageing where required.
Hydrogen embrittlement must also be reviewed. Non-electrolytic deposition avoids hydrogen generation during deposition, but pretreatment, material and process controls still matter; no generic process is automatically approved for high-strength fasteners.

20 Years Outdoor

Long service life
requires application evidence

SST hours do not directly convert to outdoor service years. Select a qualification program based on site exposure, design life and the maintenance plan.

Table 2

Available corrosion references

Read results with specimen and acceptance conditions
ReferenceConditionsReported resultEvidence type
1,000-hour salt spray comparisonCustomer's test facilitySide-by-side HDG and Innozinc specimens, including scratchesNo red rust at Innozinc scratchesHDG comparison: red rust +++Customer in-house evaluation
Five-month service observationInstalled marine hardwareNo visible corrosion reportedVisual observation, not lifetime measurement
Corrosion after damageHammer impact, bending and abrasionNo rust observed at tested impact / bend areasLocalized corrosion at abrasion; no spread during the evaluationIn-house testing
Salt spray guidance: Innozinc-hHigh-corrosion-resistance grade1,500–2,000 hrGrade guidance; confirm test report and conditions
Angles and channels: production referencesTelecom supports and building reinforcementGeneral Innozinc; not ESS-specific qualificationProduction referenceManufacturing experience, not system qualification
Special-container structural componentsHydrogen-transport container structuresFrames, brackets and pipes; references from February 2025Supply referenceComparable components; separate ESS review
15–20-year outdoor validationNot established by these references
ESS-specific qualificationConfirm for the proposed applicationComponent similarity is not qualification

Manufacturing experience and ESS qualification are different. Angles, channels and frames are established production geometries for telecom and construction applications. Drawings and maximum dimensions still require line-capacity review.
Those references are not ESS service validation. Confirm the current ESS sample and qualification status for your project. Neither a production reference nor SST alone establishes 20-year durability.

Plan qualification around lifecycle requirements, including operation & maintenance. Do not convert 1,000-hour SST into a promised service life.
Agree site-specific testing and long-term observations on representative production components.

Door gear Installed marine reference
Innozinc-coated door-gear cam
ESS door gear can have similar geometry to marine hardware. The 1,000-hour result is a supporting reference, not automatic ESS approval.
Hook and handle Installed marine reference
Innozinc-coated door-gear hook
Operating conditions differ. Review opening cycles, handling loads and site exposure rather than assuming a marine test covers every ESS requirement.
Inside the Enclosure

Internal components:
review contamination risks

Set electrical safety, particle-control and whisker requirements before selecting coatings for internal racks, trays and supports.

Zinc whiskers Design consideration

Zinc whiskers can grow from some zinc-coated surfaces. These metallic filaments are electrically conductive and may create faults if detached near electronics.

Assess particle pathways, enclosure design and equipment requirements for the actual ESS installation.

Whisker suppression Not established Qualification required

No Innozinc whisker-suppression claim is made here. Supporting validation has not been provided.

Do not infer suppression or electrical insulation from the ceramic/inorganic coating description.

Recommended review Before specification approval

For internal racks, cable trays, rods and hangers, define whisker and contamination requirements first.

Request the technical background guidance and agree any additional testing with the equipment designer.

Additional candidates Subject to qualification

Earthing-bar brackets require measured electrical continuity and contamination review. No coating family should be accepted or excluded by name alone.

External bases, frames and anchors need their own corrosion, damage, load and material-grade assessment.

Application

Component-specific guidance

Choose specifications by exposure and function, not one coating for the complete enclosure.

Door-gear cam
Door gear and cams
Hook handle
Hinges, hooks and handles
Bracket
Brackets and holders
Threaded rod
Threaded rods and hangers
Threaded-rod detail
Rack-frame fasteners
U-bolts
Pipe and conduit supports
Washers
Washers and small parts
Rack plating line
Cable trays and channels
Table 3

ESS component review matrix

Candidate specifications and required checks
AreaComponentCandidate specificationSupporting reference / qualification need
Enclosure exteriorDoor gear, hinges, locks and keepersInnozincComparable marine hardware; confirm component-specific requirements
Exterior: coastal, island and offshore sitesAs aboveInnozinc-hReview salt exposure and galvanic interfaces
Enclosure structureAngles, channels and framesInnozinc-h Start with qualification samplesProduction geometry references in telecom / construction; confirm ESS sample acceptance
Enclosure exteriorLouvres, vent frames and cable-gland bracketsInnozincAssess cut-edge protection and dimensional fit
Foundation / baseAnchor bolts, base frames and skidsInnozincReview field cuts, loads and repair procedure
Interior: electrical continuity requiredEarthing-bar brackets and bonding hardwareInnozincConfirm measured resistance under specified assembly conditions
Interior: near electronicsBattery rack frames, trays and threaded rodsPrior technical reviewDefine whisker and contamination requirements
All locationsHigh-strength fasteners, class 10.9 and aboveNot recommended without qualificationNo supporting hydrogen embrittlement validation provided
All locationsSliding surfaces under repeated metal-to-metal wearPrior application reviewAssess coating thickness and wear independently
Application limits

Four qualification priorities

Confirm these requirements before production approval or installation.

① High-strength fasteners (class 10.9+) Qualification required

Innozinc uses an electroplating process. Protection against hydrogen embrittlement is not established here; supporting high-strength fastener validation has not been provided. Review alternative processes with the designer, including pretreatment and process-control requirements.

② Contact resistance Testing required

The coating structure does not establish the actual joint resistance in mΩ. Agree measurement on your parts at the specified tightening torque and after relevant environmental ageing.

③ Zinc whiskers Suppression not established

For internal components near electronics, review the whisker guidance and equipment requirements. Agree appropriate evidence before approving a coating.

④ ESS-specific qualification Confirm project status

Angles and channels have production references in telecom and construction; these do not establish ESS service performance. Confirm the project's sample and approval status.

Available corrosion references include marine and special-container applications. Separate evidence is needed for ESS operation and long-term durability.

Application candidates For technical review

Candidates include angles and structural channels, door gear and exterior frames, base frames and anchors, and bonding hardware. Agree material, mechanical, electrical and exposure requirements before sample evaluation.

Evidence

Technical documents
for your review

Use supporting documents to define the qualification plan with your design and quality teams.

Table 4

Supporting documents and qualification needs

Availability subject to disclosure permissions
Evaluation topicSupporting documentEvidence typeAvailability
No scratch red rust at 1,000 hr in the cited testShipping customer's in-house test (June 2025)Customer evaluationReport available
No rust at tested impact / bend areasKEMP damage-condition evaluationIn-house evaluationIn-house photographs available
26-analyte screening; confirm report scope and detection limitsThird-party analysisThird-party reportTest report available
Metallic zinc beneath inorganic coatingElectrodeposited zinc + inorganic layerDoes not prove assembled-joint continuityCoating-system descriptionNot a contact-resistance measurement
Assembled-joint resistance (mΩ)Test under agreed component conditions
Whisker mitigation reviewNo suppression claim; review guidance available
15–20-year outdoor validationNot established; no SST-to-years conversion
Angle / channel production referencesTelecom supports and building reinforcementGeneral Innozinc; not ESS qualificationProduction referenceProduction reference
Special-container structural supplyHydrogen-transport structures; references from February 2025Frames, brackets and pipes; general InnozincSupply referenceSupply reference
ESS component supply planningDrawings and component specificationsProduction volume and delivery scheduleProject-specific plating and supply specifications
ESS enclosure long-term performance validationNot established; no SST-to-years conversion
Hydrogen embrittlement qualificationISO 15330Validation not provided; qualification required

Agree the evidence needed for approval, including operation & maintenance requirements. Manufacturing references do not replace qualification. Discuss component, electrical and environmental testing with KEMP and your design team.

How it works

Evaluate your own components

Agree a sample plan and assess coated parts against your inspection and acceptance criteria.

1

Technical documents Availability to be confirmed

Request coating comparisons, damage-evaluation photographs and whisker guidance. Share the component and intended exposure so relevant documents can be identified.

2

Sample coating Schedule to be agreed

Agree representative parts, sample quantity, fees, shipping and turnaround before dispatch.

3

Resistance and corrosion testing By agreement

Define joint-resistance criteria and exposure testing with your engineering team. Review sample results before production approval.

FAQ

Frequently asked questions

Questions from design and quality teams.

What ESS-specific experience can be confirmed?
Confirm the current project-specific qualification status with KEMP. Angles, channels and frames have production references in telecom supports and building reinforcement.
Hydrogen-transport container structures include frames, brackets and pipes supplied from February 2025.
ESS samples and acceptance requirements need separate review. Comparable manufacturing experience is not ESS system qualification.
Is earthing and bonding continuity guaranteed?
No. The electrodeposited zinc and inorganic coating structure alone cannot establish electrical continuity.
Joint resistance depends on contact preparation, geometry and assembly. Agree measurement at the specified torque, including relevant ageing, before approving the bonding connection.
Can zinc-coated parts be used near ESS electronics?
Review the equipment's contamination and whisker requirements. Conductive zinc whiskers may create electrical faults if detached near electronics.
Innozinc whisker suppression is not established here. For internal components, define acceptance criteria and required evidence with the equipment designer before selecting a coating.
Does the coating guarantee 15–20 years outdoors?
No such guarantee is established by these references. SST hours do not directly predict outdoor service years.
The cited container test recorded no scratch red rust at 1,000 hr; Innozinc-h grade guidance is 1,500–2,000 hr under specified test conditions. Agree site-specific qualification and long-term observations for the ESS project.
How should it be compared with zinc flake coating?
Compare assembled-joint electrical resistance, the complete thermal process and damage / cut-edge protection under equivalent conditions.
Non-electrolytic deposition can be relevant to embrittlement control, but pretreatment, material and process controls still require assessment. Neither coating family provides automatic approval for high-strength fasteners.
Can large panels and frames be processed?
Reference rack-line capacity is 35 tonnes/day, dependent on geometry and loading. Send drawings and maximum dimensions to confirm tank fit and handling requirements. Ambient-temperature electrodeposition reduces heat-related distortion risk, but does not eliminate every dimensional risk.
Technical review · Sample terms by agreement

Start with a representative part.
Agree the evaluation requirements.

  • Request available KTR third-party reports and the technical catalogue.
  • Discuss sample coating and agree fees, shipping and turnaround before dispatch.
  • Check threaded parts with your specified thread gauges.
  • Share the strength class so we can review application limits.
  • Please provide material, part dimensions, quantity and intended exposure where available.
Download Catalogs · English PDF
We will email you the review details and next steps.
Prefer to call? Sales: Kyungdong Ko +82-52-289-1155
You can also request technical reports by email.
Explore KEMP

Explore other applications

Find the service environment and technical review points closest to your project.

Related products
Call Our Team Sample Request